48 V DC power for telecom and data centres: rectifiers and lithium batteries, supplied from Dubai.

For more than twenty years we have supplied 48 V rectifier systems to telecom operators in Latin America. VOLT48 is now building the complete DC plant offer from Dubai — rectifiers and controller, LiFePO4 batteries matched to that rectifier, and spares for the plants you already run. We are selecting our manufacturing partners now: send us your plant and your requirement, and we will quote it as soon as the right factory is confirmed.

Normal service range of a −48 V plant ETSI EN 300 132-2
−40.5 V−57.0 V

−54.0 V 15S at full charge, inside the range

−57.6 V 16S at full charge, 0.6 V outside

Full charge at 3.60 V per cell. Whether your plant accepts either one depends on the twelve points in our compatibility checklist.

Plants and equipment we serve
  • Eltek
  • Vertiv
  • Emerson
  • Delta
  • Huawei
  • Eaton
  • Mean Well
  • ZTE

VOLT48 is an independent supplier. It is not an authorised distributor of, nor affiliated with, the manufacturers named above. All trademarks belong to their respective owners and are used here only to identify the equipment we source parts for.

15S versus 16S

A 51.2 V battery is not a 48 V battery

Telecom equipment on a −48 V bus is specified to a normal service range of −40.5 V to −57.0 V. Cell count decides whether a lithium pack stays inside that window at full charge.

Select the architecture
Energy flow in a −48 V DC plant Alternating-current mains feeds the rectifier; the rectifier feeds the −48 V bus; the bus feeds the telecom load and keeps the battery bank charged. 230 V AC AC mains AC → DC Rectifier −48 V bus Upper limit −57.0 V Telecom load 15S · 54.0 V within the window 16S · 57.6 V above the window Battery bank
Arithmetic shown for orientation. The diagram is a schematic, not a wiring drawing.
A 51.2 V battery is not a 48 V battery
Parameter15S16S
Cells in series1516
Nominal voltage (3.20 V per cell)48.0 V51.2 V
Full charge at 3.60 V per cell15 × 3.60 V = 54.0 V16 × 3.60 V = 57.6 V
Upper limit of the service range−57.0 V−57.0 V
Margin to that limit3.0 V inside0.6 V above
OrientationWithin the windowAbove the window

Service range −40.5 V to −57.0 V: ETSI EN 300 132-2 (normal service range). Cell voltages: cell-count arithmetic.

Indicative result. Actual compatibility also depends on the rectifier, controller, firmware, charge profile, temperature compensation, low-voltage disconnect and BMS.

What we supply

One supplier for the whole −48 V DC plant.

Rectifiers, batteries and spares specified together, so the battery charges correctly on the rectifier it will live with.

Rectifier systems & battery chargers

New 48 V rectifier systems, hot-swap modules, controllers and DC distribution for cell sites, repeaters, fibre nodes and data centres — from established manufacturers, sized to your load and growth.

Quoted in writing once the supplying factory is confirmed

Request a quotation

48 V LiFePO4 backup batteries

19-inch rack lithium batteries for cell and repeater sites and edge data centres. Before you order, we check that the voltage window, charge profile and BMS communications fit your rectifier and controller.

Compatibility checked before any battery is offered

See lithium batteries

Spares for installed plants

Nine product families and 28 designations, current and legacy — Eltek, Vertiv/Emerson, Huawei, Delta, Eaton, ZTE. Send the number printed on the label and we will tell you whether we can source it.

New or genuine new-old-stock only

Search the catalogue
Self-check

The twelve-point lithium compatibility checklist

Twelve points to read off your own plant before a lithium battery goes on the rectifier. The second column says where each value is read; none of it is a verdict on your site.

VOLT48
Lithium compatibility checklist
Checklist — not a site verdict
SiteYour site · one −48 V plant
PointWhere to read it
01 Rectifier module part numberRead from the module label
02 Controller model and firmware versionRead from the controller display menu
03 Output voltage range of the moduleFrom the module datasheet
04 Charge profileFloat = equalize, per battery datasheet
05 Temperature compensationSensor selection = None
06 Plant thermal runaway managementOff — protection belongs to the BMS
07 String capacityModules × Ah, entered in the controller
08 Charge current limitSet per battery, 0.1–0.5C
09 Low-voltage disconnect≥ battery disconnect + 0.5 V
10 Rectifier walk-in and default voltageSoft start enabled
11 Communications and alarm mappingProtocol, cabling, BMS version
12 Mechanical fitFrom the shelf photo
Architecture that fits15S or 16S — follows from points 03 and 04 and the cell-count arithmetic
Read every point on your own equipment before any battery is energised
Catalogue

Find your module by brand, model or part number

Nine families, 28 designations. Every card carries the identifier printed on the unit — that number is what we quote against. Product images are studio renders of generic equipment made by VOLT48, not the manufacturer’s product.

Found it? Send the number.

We answer every request in writing, including when we cannot source it.

Methodology

From a structured form to a written quotation, in four steps

Everything starts from data you can capture with a phone. No site visit is required to quote.

  1. Site details

    You send the load, the rectifier and controller already installed, or a part number and a photo of the label.

  2. Written proposal

    You receive the specification and, once the supplying factory is confirmed, a written quotation — equipment, battery compatibility, lead time, price and warranty.

  3. Hardware to order

    New or genuine new-old-stock from a qualified manufacturer, checked against the datasheet. The warranty is the one stated on the written quotation.

  4. Settings for your technicians

    The controller settings the battery datasheet requires, listed parameter by parameter, so your technicians or local contractor can apply them.

Read the engineering methodology and editorial policy

San José, CA to Dubai
From San José, California to Dubai — a career in telecom and data centre DC power
The company

Twenty years in 48 V DC power, now operating from Dubai

The experience behind VOLT48 began in San José, California, supplying 48 V DC rectifier systems and battery chargers — Delta/Ericsson, Eltek-Valere and Mean Well equipment — to telecom operators in Latin America, for cell towers, repeater sites and data centres.

VOLT48 brings that supply model from Dubai to the GCC, the wider Middle East and Africa, India and Latin America: rectifiers and batteries from established manufacturers, specified together.

  • 20+ years field experience
  • 48 V DC specialist
  • Rectifiers + lithium backup
  • China & Taiwan sourcing
Contact

Describe the site. We answer every request in writing.

Replacement module, full DC plant, lithium retrofit or a project quotation — send the details and we respond with scope, lead time and price stated in writing.

Phone & WhatsApp

Based in

Dubai, UAE — serving GCC, MEA, India & Latin America

Asking whether your plant can charge lithium? Start with our compatibility checklist: the rectifier, the controller and the firmware version come first, because without those three nobody can answer you.

We answer every request in writing, including the ones we cannot fill. Your details are used only to answer you.