48 V in AI data centers vs telecom −48 V: same number, different system
No. Both are called 48 V, but an AI rack built to OCP Open Rack V3 runs a positive busbar at 51 V or 54 V nominal with a narrow tolerance (46–52 V or 52–56 V), while a telecom plant runs −48 V with the positive pole earthed and a wide window of −40.5 V to −57.0 V. The rectifier and lithium technology overlaps; the equipment is not interchangeable until polarity, earthing and voltage window are checked.
Key figures at a glance
| Parameter | Value | Where it comes from |
|---|---|---|
| Telecom −48 V service range | −40.5 V to −57.0 V | ETSI EN 300 132-2 |
| Telecom polarity | Positive pole earthed; −48 V is the live conductor | Telecom DC plant practice |
| Open Rack V3, option 1 | 51 V DC nominal · IT gear accepts 46–52 V | OCP Open Rack V3 Base Spec rev 1.1, §12.1 |
| Open Rack V3, option 2 | 54 V DC nominal · IT gear accepts 52–56 V | OCP Open Rack V3 Base Spec rev 1.1, §12.1 |
| Open Rack V3 return | 48 V return (negative) not grounded to the power shelf frame | OCP Open Rack V3 Power Shelf rev 1.0 |
| 12 V → 48 V at the same power | ¼ of the current · 1/16 of the conduction loss | P = V × I and P = I² × R |
| Where 54 V in-rack runs out | Racks above 200 kW; a 1 MW rack would need up to 200 kg of copper busbar | NVIDIA, May 2025 |
| What comes next for AI racks | 800 V DC to the rack from 2027, converted to 54 V / 12 V inside it | NVIDIA, May 2025 |
Why both are called 48 V
In telecom, 48 V is the nominal voltage of a lead-acid string of 24 cells at 2 V each, floated directly on the DC bus with the positive pole earthed — which is why the bus reads −48 V. Data centers adopted the number much later and for a different reason: Google has run 48 V racks since 2010 and shared the design through the Open Compute Project in 2016, because feeding 48 V to the server and converting once near the load wastes less than distributing 12 V. Today's AI racks follow OCP Open Rack V3, whose busbar delivers 51 V or 54 V nominal. Same class name, two different electrical systems.
Three differences that decide whether equipment can cross over
Polarity and earthing. A telecom plant earths its positive pole and the load sees −48 V. In Open Rack V3 the busbar is positive and the specification says the 48 V return (negative) shall not be grounded to the power shelf frame. Connecting one to the other without a designed interface puts the earth reference in the wrong place.
Voltage window. Telecom equipment must run anywhere from −40.5 V to −57.0 V, because the battery sits on the bus and the voltage falls as it discharges. Open Rack V3 IT gear is specified to a narrow band around the setpoint: 46–52 V for the 51 V option, 52–56 V for the 54 V option.
Where the battery lives. A telecom site keeps one battery bank on the DC bus of the whole plant. Open Rack V3 has its own specification for battery backup units that sit in the rack, on the busbar.
Why AI racks moved to 48 V — and why they are now outgrowing it
At the same power, four times the voltage means a quarter of the current, and conduction loss falls with the square of the current: one sixteenth of the loss in the same copper. That is the whole case for 48 V over 12 V. The same physics now works against 54 V at AI densities. NVIDIA writes that today's AI racks rely on 54 V in-rack distribution, that this begins to hit physical limits above 200 kW, and that a single 1 MW rack at 54 V would need up to 200 kg of copper busbar. Its answer is 800 V DC delivered to the rack from 2027, with DC/DC conversion inside the rack down to 54 V or 12 V for the GPUs. The 48 V class does not disappear; it moves inside the rack.
What does carry across from telecom
The building blocks are related. Both worlds use hot-swappable AC/DC rectifier modules in a shelf with N+1 redundancy, and both are moving their backup from lead-acid to LiFePO4. The cell-count arithmetic also transfers: a 16S LiFePO4 pack (51.2 V nominal) asks for 57.6 V at full charge, above both the telecom upper limit of 57.0 V and the 56 V ceiling of the Open Rack V3 54 V option, while a 15S pack asks for 54.0 V. What does not transfer is the equipment itself: a telecom rectifier shelf, controller and battery string are built for a positive-earthed −48 V bus and its wide window, not for an Open Rack V3 busbar.
Edge and telecom-hosted data rooms
The two systems meet in edge data centers and in server rooms inside telecom buildings, where IT equipment is fed from the site's −48 V plant. That works when the servers and switches are bought with −48 V DC input power supplies, rated for the telecom window. Before connecting anything, confirm three things on the datasheet of each power supply: the input polarity it expects, the input voltage range against −40.5 V to −57.0 V, and how its return is referenced to earth. VOLT48 supplies the −48 V side — rectifiers, controllers and LiFePO4 banks for these plants; it does not supply Open Rack V3 power shelves.
How it is calculated
- Power is voltage times current (P = V × I): at the same power, 48 V carries a quarter of the current of 12 V.
- Conduction loss is current squared times resistance (P = I² × R): a quarter of the current gives one sixteenth of the loss in the same conductor.
- Example: 12 kW is 1,000 A at 12 V and 250 A at 48 V.
Equipment this guide covers
Common questions about this family
Can I feed an Open Rack V3 rack from a telecom −48 V plant?
Not directly. The polarity relative to earth is reversed and the telecom window of −40.5 V to −57.0 V is far wider than the 46–52 V or 52–56 V the rack equipment is specified for. It needs a conversion stage designed for that purpose, or the rack's own Open Rack V3 power shelf.
Is 54 V the same as 48 V?
Both belong to the 48 V class. In Open Rack V3, 54 V is the nominal of the second option, with IT gear rated 52–56 V. In a telecom plant, a value around 54 V is a typical float setting of a −48 V bus, not a different system.
Does 800 V DC make 48 V obsolete?
Not inside the rack: NVIDIA's own description converts 800 V to 54 V or 12 V within the rack before the GPU. And it does not touch telecom: −48 V equipment is specified by ETSI EN 300 132-2, which an AI rack architecture does not change.
Limitations
This guide compares published specifications. It does not state that any specific server power supply, Open Rack V3 power shelf or telecom plant is compatible with another: polarity, earthing and input range are confirmed per equipment from its own datasheet. NVIDIA figures are the company's own published estimates.
Sources
- ETSI EN 300 132-2 — Power supply interface at the input of ICT equipment; Part 2: −48 V DC (normal service range −40.5 V to −57.0 V)
- Open Compute Project — Open Rack V3 Base Specification, revision 1.1, §12.1 Input Voltage Specification (51 V option: 46–52 V; 54 V option: 52–56 V)
- Open Compute Project — Open Rack V3 Power Shelf specification, rev 1.0 (48 V return not grounded to the shelf frame)
- NVIDIA Technical Blog — NVIDIA 800 V HVDC architecture will power the next generation of AI factories (20 May 2025)
- Google Cloud Blog — Google and Facebook share proposed new Open Rack standard with 48 V power architecture (5 August 2016)
- Datasheet of the specific rectifier module and of the specific battery model quoted (no public URL — cite by title)
Editorial and technical methodology →
Other guides
- Is the Emerson R48-2900U the same as the Vertiv R48-2900U?
- Can I mix R4850G2 and R4875G1 modules in the same shelf?
- What float voltage do I set for lithium on a Flatpack2?
- Can I put a 51.2 V rack battery in my −48 V telecom plant?
- How do I disable temperature compensation on a NetSure controller?
- Is the Eltek Flatpack2 discontinued?
- Where do I set the low-voltage disconnect on a lithium retrofit?
- What paperwork does a telecom lithium battery need to ship?
- How do I identify my 48 V DC plant?
- Does my controller need a firmware update before a lithium retrofit?
- How does a lithium BMS talk to a telecom DC plant?
- How much lithium replaces a 48 V VRLA bank?
- Does the grounding scheme change when I retrofit a −48V plant to lithium?
- Can I reuse the old breaker when I swap VRLA for lithium?
- Can a VRLA string and a lithium string run in parallel during a migration?
- Can I switch my −48 V plant from lead-acid to lithium? The 12-point checklist