Vertiv R48-3500e3: specifications and which module replaces it

Short answer

The R48-3500e3 is a 3500 W, −48 V DC Vertiv eSure rectifier (spec number 1R483500e3): 73 A maximum, full power from 176 to 305 VAC and up to +45 °C. It is not the same module as the R48-3500e — same rating, different body. Vertiv markets the R48-3500E4 as its backward-compatible replacement, but the E4 accepts 85–264 VAC, so on a 277 VAC feed it is not a like-for-like swap.

Key figures at a glance

ParameterValueWhere it comes from
Spec / model number 1R483500e3 / R48-3500e3 Vertiv R48-3500e3 manual
Output −48 V DC nominal, positive ground; adjustable −42 to −58 V DC via the controller Vertiv R48-3500e3 manual
Output power / current 3500 W (73 A) at 208/220/230/240/277 VAC and −48 V DC Vertiv R48-3500e3 manual
Current limit Settable 0 to 73 A via the controller Vertiv R48-3500e3 manual
AC input, nominal 208 / 220 / 230 / 240 / 277 VAC, single phase, 50/60 Hz Vertiv R48-3500e3 manual
AC input, permitted 85–305 VAC; full 3500 W from 176 to 305 VAC; 1500 W at 85 VAC Vertiv R48-3500e3 manual
Maximum input current 21.0 A at 176 V (208/240 V nominal) · 15.7 A at 235 V (277 V nominal) Vertiv R48-3500e3 manual
Efficiency ≈95–96.5 % from 25 % to 100 % load (typical tables) Vertiv R48-3500e3 manual
Temperature Full power −40 to +45 °C; 3200 W at +50 °C; 2700 W at +65 °C Vertiv R48-3500e3 manual
Altitude 2000 m at full power; above that, derate 3 °C per 300 m up to 4000 m Vertiv R48-3500e3 manual
AC protection Low-voltage disable 80 V ±5 V · high-voltage disable 307.5 V ±2.5 V Vertiv R48-3500e3 manual
Output fuses Two 63 A fuses in the output, not customer replaceable Vertiv R48-3500e3 manual
High-voltage shutdown Adjustable 56–59 V DC via controller; backup 59.5 V ±0.5 V Vertiv R48-3500e3 manual
Controller link / paralleling CAN bus · up to 160 rectifiers in one system · active load sharing Vertiv R48-3500e3 manual
Hot swap Yes, insert or remove on a live DC system Vertiv R48-3500e3 manual
Dimensions / weight 42.0 × 84.5 × 330 mm (H × W × D) / 1.7 kg Vertiv R48-3500e3 manual
Compliance (as stated by Vertiv) EMC: ETSI EN 300 386, FCC Part 15 class B, GR-1089-CORE · Safety: IEC/EN 60950 Vertiv R48-3500e3 manual

e, e3 or E4: which one do you actually have?

Three Vertiv eSure modules carry "3500" in the name, and the front label is usually all a buyer searches. The body is what decides whether a module fits the shelf.

R48-3500eR48-3500e3R48-3500E4
Part number1R483500E1R483500e31R483500E4
Body (H × W × D)132 × 85.3 × 217 mm42.0 × 84.5 × 330 mm41 × 84.5 × 330 mm
Weight3.5 kg1.7 kg1.9 kg
AC input, nominal200–277 VAC208–277 VAC200–250 VAC
AC input, permitted85–305 VAC85–305 VAC85–264 VAC
Max input current22.5 A21.0 A21 A
DC output range−42 to −58 V−42 to −58 V−42 to −57.6 V
Output3500 W / 73 A3500 W / 73 A3500 W / 73 A
Peak efficiency96.3 %≈96.5 % (typical tables)98 %
Controller linkCAN busCAN busCAN bus
Fits an e3 shelf?No: different body—Yes, per Vertiv

e → e3 (or e3 → e): not a swap. The bodies differ in height and depth, so the shelf is different. A site with "e" modules needs "e" modules or a shelf change.

e3 → E4: Vertiv's E4 datasheet describes it as backward compatible and able to replace R48-3500E3 rectifiers. Before ordering, confirm the AC feed stays within 264 VAC and that the controller recognises the E4 (read the controller model and software version on its display).

Mixing e3 and E4 in one plant: the E4 datasheet describes mixing standard and high-efficiency rectifiers with ECO mode on the NetSure controller. We still confirm it against your controller version before quoting.

How the e3 behaves when the controller is lost

This is the question that matters on remote sites. Per Vertiv's manual:

  • The factory default output voltage is 53.5 V.
  • Once the controller recognises the module, the output moves to the voltage programmed in the controller.
  • If communication with an SCU+ controller is lost, the module goes to a separate default voltage programmed into it.
  • If communication with an ACU+ or NCU controller is lost, the module keeps the last float voltage it received.

On a lithium retrofit this is why the controller settings must be right before the swap: with an ACU+ or NCU controller, a module that loses the link stays at the last float value it was given (with an SCU+ it goes to its own programmed default voltage). See the 12-point lead-acid to lithium checklist.

Reading the LEDs before you order a replacement

LEDStateMost common cause (Vertiv manual)
GreenOffNo AC input, or internal input fuse open
GreenFlashingController is identifying the module
YellowOnAC input out of range, over-temperature, power derating, module not fully inserted, load-sharing imbalance, or ECO standby
YellowFlashingLost communication with the controller (module still supplies power)
RedOnOutput disabled (for example HVSD or internal output fuse open), severe sharing imbalance, address conflict
RedFlashingFan not operating: the module shuts down; the fan is field replaceable

A flashing red LED points to the fan, not necessarily a dead module. A yellow LED in summer heat can simply be thermal derating above +45 °C.

Before you change or add an e3

  1. Photograph the module label (model and spec number), not the cabinet brand.
  2. Photograph the controller display with its model and software version.
  3. Note the AC feed voltage (208 / 230 / 240 / 277 V): it decides whether an E4 is an option.
  4. After inserting a module, check the per-module current limit: the controller divides the total limit by the number of modules, and Vertiv warns not to set it so low that losing one module drops the limit below the load.
  5. If the site is moving from VRLA to lithium, follow the 12-point list before touching float, HVSD or current limit.

Not sure what the plant is? Identify your DC plant in two photos. The naming history is in Emerson R48-2900U vs Vertiv R48-2900U, and the wider family in Vertiv NetSure & Emerson R48 modules.

Need an R48-3500e3, an E4 or an e?

Send a photo of the module label and of the controller display, plus the AC feed voltage. We tell you in writing which module matches and whether an E4 is an option on your site. Source, availability and lead time are confirmed per request, never promised in advance.

Request a quotation → · Phone & WhatsApp: +971 58 829 2878

Equipment this guide covers

Common questions about this family

What is the difference between the R48-3500e and the R48-3500e3?

Same 3500 W and 73 A rating, different module. The e is 132 mm tall and 217 mm deep; the e3 is 42 mm tall and 330 mm deep. They are not interchangeable in the same shelf.

Can the R48-3500E4 replace an R48-3500e3?

Vertiv's E4 datasheet says it is backward compatible and replaces R48-3500E3 rectifiers. Check that your AC input is within the E4's 85–264 VAC range and that your controller recognises it.

Does the R48-3500e3 work on 277 VAC?

Yes. 277 VAC is one of its nominal inputs (Vertiv notes 277 VAC applies to the e3 only), with a permitted range up to 305 VAC.

What is the R48-3500e3 output current?

73 A at −48 V DC, 3500 W. The current limit is adjustable from 0 to 73 A through the controller.

Why is my R48-3500e3 giving less than 3500 W?

It derates above +45 °C ambient (3200 W at +50 °C, 2700 W at +65 °C) and below 176 VAC input (1500 W at 85 VAC). The yellow LED lights when it is derating.

What does the flashing red LED mean on an R48-3500e3?

The fan has stopped and the module has shut down. The fan is field replaceable.

Is the R48-3500e3 hot swappable?

Yes. Vertiv rates it for insertion or removal on a live DC system.

What is the part number of the R48-3500e3?

The spec number is 1R483500e3. The R48-3500e is 1R483500E and the E4 is 1R483500E4: quote the full number when you ask for a price.

Limitations

This page reproduces manufacturer figures from Vertiv's own manual and datasheets. It does not state which NetSure system or shelf a given site uses, and it does not guarantee that a module will be recognised by a particular controller version: that is read per site from the label and controller photos.

Sources

  1. Vertiv — eSure Rectifier Module User Manual, R48-3500e3 (spec. no. 1R483500e3), Rev B
  2. Vertiv — eSure Rectifier R48-3500e datasheet (2017.03)
  3. Vertiv — eSure Rectifier R48-3500E4 datasheet (R02/2021)

Editorial and technical methodology →

Before you buy a battery, find out what your plant can charge.

Twelve points decide whether a lithium battery is safe on your rectifier. Check them on your plant with our compatibility checklist.

See the compatibility checklist →